How should insert type electromagnetic flowmeter be installed?

The insert type electromagnetic flowmeter is an instrument used to measure conductive liquids, especially for large diameter pipe measurements.

Rated 4.8/5 based on 577 customer reviews
Share:
Content

For the installation of the flow meter may not be understood by many people, next we will talk about the installation method of insert type electromagnetic flow meter.

1, should be installed in the sensor installation upstream straight pipe section is not less than 5D (D: pipe diameter), the downstream straight pipe section is not less than 2D place.

2, when the sensor is inserted into the pipeline, the Angle between the vertical diameter of the pipeline section should be less than 5°, which is suitable for measuring the cleaning medium with small pipeline vibration.

3, the installation of the sensor should first clean the welding slag and burr of the installation base of the tested pipe.

4, then turn off the upstream flow control valve or use low pressure water supply.

5. Install the DN50 ball valve on the mounting base. Note that the long cavity of the ball valve is upward, check whether the ball valve can be fully opened and fully closed, and install the compression screw seat, compression nut and rubber sealing ring on the ball valve. Loosen the positioning nut.

6. Insert the sensor rod into the pipeline under test through the ball valve, and note that the direction of the sensor sign rod should be consistent with the flow direction of the fluid.

Inquiry


    More Electromagnetic Flow Meter

    Electromagnetic flowmeter is a speed meter to measure the volume flow of conductive media. While carrying out on-site monitoring and display, it can output standard current signals for recording, adjustment and control, realizing automatic control of detection, and realizing long-distance transmission of signals. It can be widely used in water, chemical, coal, environmental protection, textile, metallurgy, paper and other industries in the flow measurement of conductive liquid. The structure of the instrument has one type and one type.

    Performance Technical parameter
    Size DN3-DN3000mm
    Nominal Pressure 0.6-1.6Mpa(2.5Mpa/4.0Mpa/6.4Mpa…Max 42Mpa)
    Accuracy +/-0.5%(Standard)     +/-0.3% or +/-0.2%(Optional)
    Liner PTFE, Neoprene, Hard Rubber, EPDM, FEP, Polyurethane, PFA
    Electrode SUS316L, Hastelloy B, Hastelloy C       Titanium, Tantalum, Platinium-iridium
    Structure Type Integral type, remote type, submersible type, ex-proof type
    Medium Temperature -20~+60 degC(Integral type)
    Remote type ( Neoprene ,Hard Rubber ,Polyurethane ,EPDM) -10~+80degC
    Remote type(PTFE/PFA/FEP) -10~+160degC
    Ambient Temperature -20~+60deg C
    Ambient Humidity 5-100%RH(relative humidity)
    Measuring Range Max 15m/s
    Conductivity >5us/cm
    Protection Class IP65(Standard); IP68(Optional for remote type)
    Process Connection Flange (Standard), Wafer, Thread, Tri-clamp etc (Optional)
    Output Signal 4-20mA/Pulse
    Communication RS485(Standard), HART(Optional),GPRS/GSM (Optional)
    Power Supply AC220V (can be used for AC85-250V)
    DC24V (can be used for DC20-36V)
    DC12V (optional), Battery Powered 3.6V (optional)
    Power Consumption <20W Alarm Upper Limit Alarm / Lower Limit Alarm Self-diagnosis Empty Pipe Alarm, Exciting Alarm Explosion Proof ATEX