The selection of electromagnetic flow timing can not be ignored

Electromagnetic flowmeter selection is generally more concerned with the measurement medium, temperature, pressure, connection form, protection level and whether explosion-proof.

Rated 4.9/5 based on 311 customer reviews
Share:
Content

Electromagnetic flowmeter selection is generally more concerned with the measurement medium, temperature, pressure, connection form, protection level and whether explosion-proof. Although there is also concern in the range, but because the electromagnetic flowmeter is a linear instrument, the range can be adjusted online according to user requirements, without re-calibration, so many people ignore the importance of the range.

The range, that is, the measurement range, is a very key factor in whether the electromagnetic flowmeter can be better used. Although the electromagnetic flowmeter is linear, the range is adjustable, and there is no starting flow rate. However, due to the instability of the electromagnetic flowmeter at low flow rates, the accuracy will greatly deteriorate as the flow rate is reduced to a certain value (according to the flow curve, generally around 0.5m/s, which is the inflection point). Despite the metrological display and output, the accuracy of calibration can no longer be guaranteed. Therefore, the lower limit value of the electromagnetic flowmeter is a condition that cannot be ignored when selecting. The flow range of some production enterprises is written from 0, in fact, this is a misunderstanding, because according to the flow curve, 0 will be displayed and output, but the accuracy will be much greater than 0.3% or 0.5%.

Therefore, when selecting the electromagnetic flowmeter, it is necessary to ensure that the use range meets the lower limit requirements of the manufacturer, the common flow rate is 60%-80% of the upper limit of the range given by the manufacturer, and the low use flow rate does not exceed the lower limit of the manufacturer, which can ensure the accuracy and ensure the extension of the upper limit of the flow rate.

Since the electromagnetic flowmeter is linear, the increase of the upper limit flow will not affect the accuracy, so for those users who reserve flow, as long as the lower limit flow can be calculated.

Inquiry


    More Electromagnetic Flow Meter

    Electromagnetic flowmeter is a speed meter to measure the volume flow of conductive media. While carrying out on-site monitoring and display, it can output standard current signals for recording, adjustment and control, realizing automatic control of detection, and realizing long-distance transmission of signals. It can be widely used in water, chemical, coal, environmental protection, textile, metallurgy, paper and other industries in the flow measurement of conductive liquid. The structure of the instrument has one type and one type.

    Performance Technical parameter
    Size DN3-DN3000mm
    Nominal Pressure 0.6-1.6Mpa(2.5Mpa/4.0Mpa/6.4Mpa…Max 42Mpa)
    Accuracy +/-0.5%(Standard)     +/-0.3% or +/-0.2%(Optional)
    Liner PTFE, Neoprene, Hard Rubber, EPDM, FEP, Polyurethane, PFA
    Electrode SUS316L, Hastelloy B, Hastelloy C       Titanium, Tantalum, Platinium-iridium
    Structure Type Integral type, remote type, submersible type, ex-proof type
    Medium Temperature -20~+60 degC(Integral type)
    Remote type ( Neoprene ,Hard Rubber ,Polyurethane ,EPDM) -10~+80degC
    Remote type(PTFE/PFA/FEP) -10~+160degC
    Ambient Temperature -20~+60deg C
    Ambient Humidity 5-100%RH(relative humidity)
    Measuring Range Max 15m/s
    Conductivity >5us/cm
    Protection Class IP65(Standard); IP68(Optional for remote type)
    Process Connection Flange (Standard), Wafer, Thread, Tri-clamp etc (Optional)
    Output Signal 4-20mA/Pulse
    Communication RS485(Standard), HART(Optional),GPRS/GSM (Optional)
    Power Supply AC220V (can be used for AC85-250V)
    DC24V (can be used for DC20-36V)
    DC12V (optional), Battery Powered 3.6V (optional)
    Power Consumption <20W Alarm Upper Limit Alarm / Lower Limit Alarm Self-diagnosis Empty Pipe Alarm, Exciting Alarm Explosion Proof ATEX